2.0 S ETTING
THE
S WITCHES
The meter has switches that must be checked and/or changed prior to
applying power. To access the power switch, remove the meter base from the
case by firmly squeezing and pulling back on the side rear finger tabs. This
should lower the latch below the case slot (which is located just in front of the
finger tabs). It is recommended to release the latch on one side, then start the
other side latch.
Power Selection Switch
Caution: Insure the AC power selection switch is set for the
proper voltage before powering-up the meter. The meter is shipped
from the factory in the 230 VAC position.
Set-Up DIP Switches
A DIP switch is located at the rear of the meter,
and is fully accessible when the unit is in the case.
It is used for the selection of the input parameters
SWITCH 3
HI Frequency : Removes damping capacitor and allows max. frequency.
LO Frequency : Limits input frequency to 50 Hz and input pulse widths
to 10 msec.
SWITCH 4
LOGIC : Input trigger levels V IL = 1.5 V max.; V IH = 3.75 V max.
MAG : 200 mV peak input (must have SRC on).
SWITCH 5
Enable Programming : Enables programming through the front panel buttons.
Disables Programming : Disables the front panel buttons from any
programming changes.
SWITCH 6
Not Active for the Rate Meter
FRONT DISPLAY
and program disable.
ON
POWER
SELECTION
1 2 3 4 5 6
SWITCH
ON
1
2
3
4
5
6
230
Factory Setting
SWITCH 1
SNK. : Adds internal 7.8 K ? pull-up resistor to + 12 VDC, I MAX = 1.9 mA.
115
SWITCH 2
SRC. : Adds internal 3.9 K ? pull-down resistor, 8 mA max. @ 30 VDC max.
REAR TERMINALS
INPUT SET-UP
DIP SWITCHES
3.0 W IRING
THE
M ETER
WIRING OVERVIEW
Electrical connections are made via screw-clamp terminals located on the
back of the meter. All conductors should conform to the meter ’s voltage and
current ratings. All cabling should conform to appropriate standards of good
installation, local codes and regulations. It is recommended that the power
supplied to the meter (DC or AC) be protected by a fuse or circuit breaker.
When wiring the meter, compare the numbers embossed on the back of the
meter case against those shown in wiring drawings for proper wire position. Strip
the wire, leaving approximately 0.3" (7.5 mm) bare lead exposed (stranded wires
should be tinned with solder.) Insert the lead under the correct screw-clamp
terminal and tighten until the wire is secure. (Pull wire to verify tightness.)
EMC INSTALLATION GUIDELINES
Although this meter is designed with a high degree of immunity to Electro-
Magnetic Interference (EMI), proper installation and wiring methods must be
followed to ensure compatibility in each application. The type of the electrical
noise, source or coupling method into the meter may be different for various
installations. The meter becomes more immune to EMI with fewer I/O
connections. Cable length, routing, and shield termination are very important
and can mean the difference between a successful or troublesome installation.
Listed below are some EMC guidelines for successful installation in an
industrial environment.
1. The meter should be mounted in a metal enclosure, which is properly
connected to protective earth.
2. Use shielded (screened) cables for all Signal and Control inputs. The shield
(screen) pigtail connection should be made as short as possible. The
connection point for the shield depends somewhat upon the application.
Listed below are the recommended methods of connecting the shield, in order
of their effectiveness.
a. Connect the shield only at the panel where the unit is mounted to earth
ground (protective earth).
b. Connect the shield to earth ground at both ends of the cable, usually when
the noise source frequency is above 1 MHz.
4
c. Connect the shield to common of the meter and leave the other end of the
shield unconnected and insulated from earth ground.
3. Never run Signal or Control cables in the same conduit or raceway with AC
power lines, conductors feeding motors, solenoids, SCR controls, and
heaters, etc. The cables should be ran in metal conduit that is properly
grounded. This is especially useful in applications where cable runs are long
and portable two-way radios are used in close proximity or if the installation
is near a commercial radio transmitter.
4. Signal or Control cables within an enclosure should be routed as far as possible
from contactors, control relays, transformers, and other noisy components.
5. In extremely high EMI environments, the use of external EMI suppression
devices, such as ferrite suppression cores, is effective. Install them on Signal
and Control cables as close to the unit as possible. Loop the cable through the
core several times or use multiple cores on each cable for additional protection.
Install line filters on the power input cable to the unit to suppress power line
interference. Install them near the power entry point of the enclosure. The
following EMI suppression devices (or equivalent) are recommended:
Ferrite Suppression Cores for signal and control cables:
Fair-Rite # 0443167251 (RLC# FCOR0000)
TDK # ZCAT3035-1330A
Steward # 28B2029-0A0
Line Filters for input power cables:
Schaffner # FN610-1/07 (RLC# LFIL0000)
Schaffner # FN670-1.8/07
Corcom # 1 VR3
Note: Reference manufacturer ’s instructions when installing a line filter.
6. Long cable runs are more susceptible to EMI pickup than short cable runs.
Therefore, keep cable runs as short as possible.
7. Switching of inductive loads produces high EMI. Use of snubbers across
inductive loads suppresses EMI.
Snubber: RLC# SNUB0000.
相关PDF资料
PB52233SLK PROJ BOARD COLDFIRE M52
PD412411 DIODE MOD ISO DUAL 2400V 1100A
PF24-30 TRANSFORMER LO PRO 15VAC 1.6A
PFT12-28 TRANSFORMER 16VCT 28VCT 12VA
PFT12-35 TRANSFORMER 16VCT 35VCT 12VA
PFT24-28 TRANSFORMER 16VCT 28VCT 24VA
PFT24-35 TRANSFORMER 16VCT 35VCT 24VA
PFT6-32 TRANSFORMER 17.5VCT 31.5VCT 6VA
相关代理商/技术参数
PAXLRT00 功能描述:METER RTD TEMP 4-DIGIT RoHS:是 类别:工业控制,仪表 >> 仪表 - 面板,数字 系列:PAX®LITE 标准包装:12 系列:* 其它名称:Q7072030
PAXLSG00 功能描述:METER STRAIN GAGE 3 1/2-DIGIT RoHS:否 类别:工业控制,仪表 >> 仪表 - 面板,数字 系列:PAX®LITE 标准包装:12 系列:* 其它名称:Q7072030
PAXLT000 制造商:Red Lion Controls 功能描述:METER, TC/RTD TEMP WITH DUAL RELAY 制造商:Red Lion Controls 功能描述:TC/RTD TEMP WITH DUAL RELAY
PAXLT0U0 制造商:Red Lion Controls 功能描述:METER, UL LISTED TC/RTD TEMP W/ D RELAY 制造商:Red Lion Controls 功能描述:UL LISTED TC/RTD TEMP WITH DUAL
PAXLTC00 功能描述:METER THERMOCOUPLE 4-DIGIT RoHS:否 类别:工业控制,仪表 >> 仪表 - 面板,数字 系列:PAX®LITE 标准包装:12 系列:* 其它名称:Q7072030
PAXLVA00 功能描述:VOLTMETER AC 3 1/2-DIGIT RoHS:是 类别:工业控制,仪表 >> 仪表 - 面板,数字 系列:PAX®LITE 标准包装:12 系列:* 其它名称:Q7072030
PAXLVD00 功能描述:VOLTMETER DC 3 1/2-DIGIT RoHS:是 类别:工业控制,仪表 >> 仪表 - 面板,数字 系列:PAX®LITE 标准包装:12 系列:* 其它名称:Q7072030
PAXOEMS1 制造商:Red Lion Controls 功能描述:SOFTWARE AND USB CABLE RS232